All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM035A-EN-P — April 2014

11

Bulletin 1606 Switched Mode Power Supplies

11. Protection Features

Output over-current protection

not included

Reverse input polarity protection included

unit does not start when input voltage is reversed

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 2.5mm

e.g. screws, small parts

Over-temperature protection

not included

Input transient protection

not included

Output transient protection

not included

Internal input fuse

not included

12. Safety Features

Input / output separation

no galvanic separation

200V epitaxial diode between input and output

Safety level of output voltage

The output voltage is regarded to be SELV (EN 60950-1) or PELV (EN 60204-1, EN
50178, IEC 60364-4-41) if the input voltage fulfills the requirements for a SELV
source or PELV source.

Class of protection

III

plastic housing, PE connection not required