Example: n+1 redundancy, Example: battery back-up – Rockwell Automation 1606-XLSPRED Power Supply Reference Manual User Manual

Page 15

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM035A-EN-P — April 2014

15

Bulletin 1606 Switched Mode Power Supplies

16.4. Example: N+1 Redundancy

A N+1 redundancy up to 6.3A requires four 16060-XLP50E power supplies (each 2.1A output current) and two
1606-XLPRED redundancy modules.

Fig. 16-2 Wiring diagram, N+1 Redundancy, 6.3A output current

L

N

I

XLP50E

Power

Supply

L N

Input

Output

+ +

- -

DC

OK

XLP50E

Power

Supply

L N

Output

Input

+ +

- -

DC

OK

XLPRED

IN 1

+

-

+

-

Output

+

- -

IN 2

+

Alarm

Monitor

Load

+

-

XLP50E

Power

Supply

L N

Input

Output

+ +

- -

DC

OK

XLP50E

Power

Supply

L N

Output

Input

+ +

- -

DC

OK

XLPRED

IN 1

+

-

+

-

Output

+

- -

IN 2

+

I

I

I

Note: Whenever possible, use separate mains systems for each power supply.

16.5. Example: Battery Back-up

A battery back-up requires one power supply and one 1606-XLPRED redundancy module.

Please note:
Set output voltage of power supply to 26.5Vdc minimum to ensure that the load current is delivered from the power
supply and not from the charger (battery). Use a fuse between the battery and the 1606-XLPRED module!

Fig. 16-3 Wiring diagram, 10A Battery back-up

L

N

PE

24V Battery

I

Battery

Charger

+

-

Failure

Monitor

Load

XLP50E

Power

Supply

L N

Input

Output

+ +

- -

DC

OK

XLPRED

IN 1

+

-

+

-

Output

+

- -

IN 2

+

Advertising