Mounting orientations – Rockwell Automation 1606-XLSPRED Power Supply Reference Manual User Manual

Page 16

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

16

Rockwell Automation Publication 1606-RM035A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

16.6. Mounting Orientations

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature.

Fig. 16-4
Mounting
Orientation A
(Standard
orientation)

Redundancy

Module

INPUT

OUTPUT

Output Current

0

10

20

30

40

60°C

2

6

8

10A

50

4

Ambient Temperature

Fig. 16-5
Mounting
Orientation B
(Upside down)

Redundancy

Module

INPU

T

OUTPUT

Output Current

0

10

20

30

40

60°C

2

6

8

10A

50

4

Ambient Temperature

Fig. 16-6
Mounting
Orientation C
(Table-top
mounting)

Output Current

0

10

20

30

40

60°C

2

6

8

10A

50

4

Ambient Temperature

Fig. 16-7
Mounting
Orientation D
(Horizontal cw)

Redun

dancy

Mo

dul

e

IN
PU
T

OUTPUT

Output Current

0

10

20

30

40

60°C

2

6

8

10A

50

4

Ambient Temperature

Fig. 16-8
Mounting
Orientation E
(Horizontal ccw)

Redundancy

M

o

du

le

IN

PUT

OUTP

U

T

Output Current

0

10

20

30

40

60°C

2

6

8

10A

50

4

Ambient Temperature