Terminals and wiring – Rockwell Automation 1606-XLSPRED Power Supply Reference Manual User Manual

Page 7

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM035A-EN-P — April 2014

7

Bulletin 1606 Switched Mode Power Supplies

6. Terminals and Wiring

Input and output

Type

Bi-stable, quick-connect spring clamp terminals.
IP20 Finger safe construction.
Suitable for field- and factory installation.

Solid wire

0.3-4mm

2

Stranded wire

0.3-2.5mm

2

American Wire Gauge

26-12 AWG

Max. wire diameter

2.8mm (including ferrule)

Wire stripping length

6mm / 0.25inch

Pull-out force

10AWG:80N, 12AWG:60N, 14AWG:50N,
16AWG:40N (according to UL486E)

Terminals shipped in open

position.

Fig. 6-1 Connecting a wire


Instructions:
a) Use appropriate copper cables that are designed for

minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.

b) Follow national installation codes and installation

regulations!

c) Ensure that all strands of a stranded wire enter the terminal

connection!

d) Ferrules are allowed, but not required.
e) Do not connect or disconnect the wires from the terminals

below -25°C (-13°F).