Chapter 3, Specifications and dimensions, Technical specifications – Rockwell Automation 1608N MiniDySC User Manual, 2-6 Amp User Manual

Page 11: Ch 3-specifications and dimensions, Chapter

Advertising
background image

Rockwell Automation Publication 1608N-UM001B-EN-P - May 2014

11

Chapter

3

Specifications and Dimensions

Technical Specifications

Table 5 - Technical Specifications – MiniDySC (2...6 Amps)

Electrical Input/Output (Normal Mode—Static Switch)

Connection Configuration

Series-connected with load. Under normal line condition, the static switch passes utility voltage directly to the load

Standard Input Voltage DySC

1Phase: 120, 208, 220, 230, 240V

Voltage Range

±10%

Current Overload
(Trip above these levels)

110% continuous, 150% @ 10 sec., 200% @ 0.5 sec., 300% @ 10 cycles, 400% @ 3 cycles, 1000% Instantaneous

Frequency

50/60 Hz Auto Sensing

Frequency Range

 USBDLJOH

45 to 65 Hz

Surge Protection Device (SPD)

Built-in 3-Layers consisting of MOVs & Capacitors

Efficiency

250 VA > 94%, 500 VA > 97%, 750 VA > 96%

Phase (wiring)

1 phase (L-L & L-N)

Detection Voltage

88.5% of rated voltage

Response Time (typical)

0.7 ms detection, 1.2 ms inverter reaction (<2ms)

Electrical Output (Sag Correction Mode—Inverter)

Output Voltage

Matches pre-sag input voltage

Voltage Regulation

±5% typical, +5% / -13% of nominal max

Output Current

Rated RMS (2A ... 6A) with 300% instantaneous peak max

Crest Factor (at rated load)

3.0

Load

Power factor range -0.5 ...+0.9, DC component <2% of rated current

Voltage Waveform (typical)

Sine wave

Voltage Sag Correction Times

Single Event

87% to 50% voltage remaining

5 seconds SR & ER

Sags to zero voltage remaining

50ms or 200ms (standard or extended run time DySCs). Based on nameplate ratings with a power factor of 0.7

Multiple Events

Max Sag Correction Time

5 seconds cumulative usage

Seqential Sag Recovery

0 seconds (assuming cumulative run-time available)

Full Recovery Time

Max 5 minutes to full recovery

Mechanical

Enclosure Ratings

NEMA 1 (IP20)

Cooling

Forced air (500VA, 750VA) or natural convection (250VA)

Access

Lower front for connections

Accessibility (Wiring)

Pluggable compression terminal block

Communications / User Interface

Indicators

3 LEDs: Overload Trip, Normal, Alarm

Connectivity

Form C contacts rated [email protected] or 30Vdc@1A

Environmental

Ambient Temperature

0 ...+50°C

Storage Temperature

-40°C ...+75°C

Relative Humidity

0 ...95% non-condensing

Altitude

Rated current available to 1000m (3300ft)

Certifications

Agency Approvals

cULus recognized, Exceeds SEMI F47 Standard

Advertising