Alarm Contact Connections

The alarm contact will change states during any alarm condition. When the

alarm condition has cleared, the alarm relay will return to its normal state.

Terminal block pin numbers and Alarm contact ratings are shown in

Figure 5

Operation is as follows:

Normal Line Condition: pin 1 connects to pin 3.

Alarm Condition: pin 1 connects to pin 2.

Power Off Condition: pin 1 connects to pin 2.

Figure 5 - Alarm Contact

Power Switch

The service disconnect or the external branch circuit breaker may be used as a

master on/off switch.

Operating Indicators

When power is switched on, the Green light (Normal) on the front of the

MiniDySC will be lighted. The green light indicates that the output voltage

is within a normal range of -13% to +10% of nominal. This indicator will

also be on during sag correction events since the MiniDySC will be

maintaining the output voltage.

The Amber light (Alarm) flashes when the MiniDySC correction function

is inhibited. See Alarm Codes section below. The MiniDySC will resume its

corrective function and the flashing light will turn off when the alarm

condition has ceased. In a flashing amber light condition, the MiniDySC

will continue to pass the utility power to the load via the static switch.

The Red light will be on when the Static switch is inhibited due to an

overload condition. The MiniDySC will open the output. Power will need to

be cycled to reset the MiniDySC.

Table 3 - List of conditions and indications

2

1

NO

NC

COM

120 VAC .5 A

Alarm Relay Rating

3

30 VDC 1A

Condition

Description

Red
Light
Status

Green
Light
Status

Amber
Light
Status

Inverter
Operation
Status

Normal

88.5% < VLINE < 110% of Nominal

Off

On

Off

Off

Sag Event

VLINE < 88.5% while MiniDySC is correcting

Off

On

Off

Running

Runtime Exceeded

Cumulative runtime exceeded

Off

On

Flashing

Inhibited

Normal Mode, Static Switch Overload

Continuous Load current > 150%

On

Off

Off

Inhibited

Inverter Run Mode, Output Over current Load current > 150% for 3 cycles

Off

On

Flashing

Inhibited



Refer to Run Time specifications in

Technical Specifications on page 11



See Static Switch Maximum Current specifications in

Technical Specifications on page 11



If red LED is on, the output of the MiniDySC is inhibited and power needs to be cycled. If the problem reoccurs, the MiniDySC is overloaded.



On, provided output is within normal range

88.5

%< VLINE <110%.



Check Alarm Codes