Chapter 2, Operation, Ground connection – Rockwell Automation 1608N MiniDySC User Manual, 2-6 Amp User Manual

Page 7: Power connections, Line connections (input), Load connections (output), Ch 2-operation, Chapter

Advertising
background image

Rockwell Automation Publication 1608N-UM001B-EN-P - May 2014

7

Chapter

2

Operation

Ground Connection

Connect the safety ground (earth) conductor to the #8-32 (4.2mm dia.)

ground stud (Refer to

Figure 3 on page 8

or

Figure 4 on page 8

).

Torque to 20 lb-in (2.3 N-m)

Note: The MiniDySC must be safety grounded according to the National Electrical Code. All local, state, and

federal regulations applicable to the installation of electrical systems apply.

Power Connections

First remove the 6-pin terminal block connector by removing two retaining

screws and pulling out. After connections are made reinstall terminal block

connector by pressing back in place and tightening the two retaining screws.

Wire Size: 26 - 12 AWG (0.13 - 3.31 mm

2

)

Wire Strip Length: 0.256" (6.5 mm)

Torque: 5 lb-in (0.6 N-m)

Line Connections (Input)

For Line-Neutral MiniDySC (part numbers ending in V2S or V2E): connect

utility L1 (hot) and N (neutral) to terminals labeled L1 (pin 5) and N (pin

6) as shown in

Figure 3 on page 8

.

For Line-to-Line MiniDySC (part numbers ending in V1S or V1E): connect

utility L1 and L2 to terminals labeled L1 (pin 5) and L2/X2 (pin 6) as

shown in

Figure 4 on page 8

.

Load Connections (Output)

For Line-Neutral MiniDySC (part numbers ending in V2S or V2E): connect

load wires to terminals labeled X1 (pin 4) and N (pin 6) as shown in

Figure 3

on page 8

.

For Line-to-Line MiniDySC (part numbers ending in V1S or V1E): connect

load wires to terminals labeled X1 (pin 4) and L2/X2 (pin 6) as shown in

Figure 4 on page 8

.