Connection Diagrams

Figure 3 - 120, 220,230, 240 Volt, 1 Phase, Line-to-Neutral Connection Diagram

1.

User-supplied service disconnect (SW1). MiniDySC must be supplied through a

single pole switch in the "hot" line, with voltage and current ratings greater than or

equal to the MiniDySC ratings.

2.

User-supplied fuse (F1). AC input must be fused. See

Table 1

for recommended

fuse.

Note: Input neutral must be connected for all 120V, 220V and 230V applications. Failure to do so may result in

damage to the MiniDySC. Do not connect to a source with an AIC rating greater than 10,000 Arms.

Table 1 - Fuse Rating

Figure 4 - 208 & 240 Volt, 1 Phase, Line-to-Line Connection Diagram

1.

User-supplied service disconnect (SW1). MiniDySC must be supplied through a

double-pole switch located in both "hot" lines, with voltage and current ratings

greater than or equal to the MiniDySC ratings

2.

User-supplied fuses (F1, F2). Both hot lines of the AC input must be fused.

See

Table 2

for recommended fuse.

Note: Do not connect to a source with an AIC rating greater than 10,000 Arms

Table 2 - Fuse Rating

MiniDySC Rating

250 VA

500 VA

750 VA

120V

6A,120V 

15A, 120V

15A, 120V

220...240V

3.2A, 250V

10A, 250V

10A, 250V

Recommended Fuses: Bussmann MDA-6  Bussmann FRN-R-15  Bussmann FRN-R-3-2/10

Bussmann FRN-R-10

MiniDySC Rating

250 VA

500 VA

750 VA

208..240V

3.2A, 250V

10A, 250V 

10A, 250V 

Recommended Fuses: Bussmann FRN-R-3-2/10 Bussmann FRN-R-10

C NC NO X1 L1 N

Input A.C.

SW1

F1

1

2

Ground

L1

Neutral

Neutral

Ground

X1

LOAD

LOAD

C NC NO X1 L1 L2/X2

Input A.C.

SW1

F1

1

2

Ground

L1

L2/X2

Ground

X1

LOAD

LOAD

F2

2

L2/X2