Brake Fault Contact Monitoring

For all brake ratings a fault contact has been provided to provide a remote
output signal to an Allen-Bradley 1336-MOD-L3, L6 or PLC. Should a
brake fuse fail, the brake thermostat trip (or for KB050 & KC050 units the
brake enable signal be lost), the brake fault contact will open.
Interconnection wiring for remote brake monitoring is provided in the
Wiring Schemes.

Brake Fuses

All dynamic brakes are internally fused to protect brake components. When
replacing brake fuses, use only the type and size specified below.

Brake Module Jumper Settings

For the Recommended Brake Configurations shown on the previous page as
well as the interconnection diagrams shown on the following pages, there
can be only one master brake to control dynamic braking. When multiple
brakes are used, only one brake can serve as the master brake to control the
remaining slave brakes.

Master Brake Module Jumper Settings

For the master brake, leave slave/master
jumper W1 factory set to master — Between
jumper positions 2 & 3.

Slave Brake Module Jumper Settings

In each slave enclosure, reset jumper W1 to
slave — Between jumper positions 1 & 2

Input Voltage Jumper Settings

For KB brakes, remember to set jumper W2
in all enclosures to correspond to the
nominal drive input voltage. Setting the
jumper between positions 1 & 2 will select
an input voltage of 415/460 volts. Setting the
jumper between positions 2 & 3 will select
an input voltage of 380 volts.

KA and KC brakes do not have input voltage
jumpers.

Dynamic Brake

Fuse

Type

Rating

KA005

F1

A50P10 or Equivalent

10A, 500V

KB005

F1

A60Q or Equivalent

5A, 600V

KC005

F1

FWP-5 or Equivalent

5A, 700V

KA010

F1

A50P20 or Equivalent

20A, 500V

KB010

F1

A60Q or Equivalent

10A, 600V

KC010

F1

FWP-10 or Equivalent

10A, 700V

KB050

F1 & F2

A70QS35 or Equivalent

35A, 700V

KC050

F1 & F2

A70QS35 or Equivalent

35A, 700V

Slave/Master

Jumper

Set to

Master

KA005-KA010
KB005-KB010
KC005-KC010

KB050
KC050

W1

W1

M

1
2
3

S

M

S

3
2
1

Slave/Master

Jumper

Set to

Slave

KA005-KA010
KB005-KB010
KC005-KC010

KB050
KC050

W1

W1

M

1
2
3

S

M

S

3
2
1

Input

Voltage
Jumper

Set to

460V

KB005-KB010

KB050

W2

460V

W2

380V

1
2
3

460V

3
2
1

V SELECT

380V