Heavy Duty Dynamic Braking

25

1336-5.64 — July, 2005

KA005-KA010, KB005-KB010 and KC005-KC010
Wiring Scheme

L1

L2

L3 +DC -DC

TB1

Drive

TB3

MOD-L3 or L6

20

STOP

19

START

START

115V AC

21

COM

22

23

24

25

COM

26

27

28

29

COM

30

ENABLE

STOP

CUSTOMER

ENABLE

2

(–) SLAVE IN.

1

(+) SLAVE IN.

4

(+) MASTER OUT

5

(–) DC BUS

3

(–) MASTER OUT

TB1

Slave

Brake

6

(+) DC BUS

1

3

4

2

TB3

2

(–) SLAVE IN.

1

(+) SLAVE IN.

4

(+) MASTER OUT

5

(–) DC BUS

3

(–) MASTER OUT

TB1

Master

Brake

6

(+) DC BUS

1

3

4

2

TB3

Brake Power Wiring
Brake Power Wiring

All DC Brake Power Wiring must be twisted pair and run in conduit separate from Control Wiring.
Minimum required DC Brake Power Wiring sizes are listed in

tables 1b

,

2b

and

3b

.

Control Wiring

All Control Wiring must be twisted pair and run in conduit separate from DC Brake Power Wiring.
Interconnection Control Wiring between the brake terminals must be twisted pair, 1

mm

2

(18

AWG) minimum.

Optional Brake Fault Contact Wiring

A separate 115V

AC power supply is required if the brake fault contacts are to be monitored.

Refer to your 1336, 1336VT, 1336

PLUS, or 1336

FORCE User Manual for wire selection and installation details.

Connect to AUX at TB3 — Terminal 24 for L6 Option — Terminal 28 for L3 Option.

The MASTER OUT terminals are factory jumpered and must remain jumpered for single brake applications.
For multiple brake applications, remove the jumpers in all but the last enclosure.

Contact is shown in a de-energized state. Contact is closed when 115V AC power is applied to TB3 and pilot relay is energized.
Loss of power or a brake malfunction will open contact.

Connect the brake frame to earth ground. Refer to the connected drive's User Manual for grounding instructions.

-BRK

Important:

Series A 1336 PLUS (A4 frames)

380-480V, 5.5-7.5

kW/7,5-10

HP, do not use the

-DC terminal for brake connection. A separate -BRK
terminal is supplied for proper brake connection.

2

(–) SLAVE IN.

1

(+) SLAVE IN.

4

(+) MASTER OUT

5

(–) DC BUS

3

(–) MASTER OUT

TB1

Slave

Brake

6

(+) DC BUS

1

3

4

2

TB3