Terminals and wiring, Lifetime expectancy and mtbf – Rockwell Automation 1606-XLP30EQ Power Supply Reference Manual User Manual

Page 10

Advertising
background image

All parameters are specified at 124V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

10

Rockwell Automation Publication 1606-RM006A-EN-P - January 2014

Bulletin 1606 Switched Mode Power Supplies

11. Terminals and Wiring

All terminals are easy to access when the power supply is mounted on the panel. Input and output terminals are
separated from each other (input below, output above) to help in error-free wiring.

Input Output

Type

screw terminals

screw terminals

Solid wire

0.5-6mm

2

0.5-6mm

2

Stranded wire

0.5-4mm

2

0.5-4mm

2

American Wire Gauge

20-10 AWG

20-10 AWG

Wire stripping length

7mm / 0.275inch

7mm / 0.275inch

Screwdriver 3.5mm

slotted

or

Pozidrive No 2

3.5mm slotted or
Pozidrive No 2

Recommended tightening torque

1Nm, 9lb.in

1Nm, 9lb.in

Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:

60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.

b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed.



12. Lifetime Expectancy and MTBF

These units are extremely reliable and use only the highest quality materials. The number of critical components such
as electrolytic capacitors has been reduced.

AC 100V

AC 120V

AC 230V

Lifetime expectancy

*)

151 000h *)

171 000h *) 174 000h *)

at 24V, 1.3A and 40°C

259 000h *)

259 000h *) 254 000h *)

at 24V, 0.65A and 40°C

386 000h *)

426 000h *) 484 000h *)

at 24V, 1.3A and 25°C

MTBF

**)

SN 29500, IEC 61709

2 123 000h

2 312 000h

2 405 000h

at 24V, 1.3A and 40°C

3 688 000h

3 971 000h

4 124 000h

at 24V, 1.3A and 25°C

MTBF

**)

MIL HDBK 217F

1 219 000h

1 270 000h

1 187 000h

at 24V, 1.3A , 40°C; Ground Benign GB40

1 611 000h

1 686 000h

1 588 000h

at 24V, 1.3A , 25°C; Ground Benign GB25

295 000h

314 000h

309 000h

at 24V, 1.3A , 40°C; Ground Fixed GF40

380 000h

405 000h

400 000h

at 24V, 1.3A , 25°C; Ground Fixed GF25

*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime

expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.

**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.