All parameters are specified at 124V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

22

Rockwell Automation Publication 1606-RM006A-EN-P - January 2014

Bulletin 1606 Switched Mode Power Supplies

20.11.Mounting Orientations

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:

Curve A1

Recommended output current.

Curve A2

Max allowed output current (results in approximately half the lifetime expectancy of A1).

Fig. 20-5
Mounting
Orientation A
(Standard
orientation)

Power

Supply

OUTPUT

INPUT

Output Power

0

10

20

30

40

60°C

6

18

24

30W

50

A1

12

Ambient Temperature

Fig. 20-6
Mounting
Orientation B
(Upside down)

Power

Supply

OUTPU

T

INPUT

Output Power

0

10

20

30

40

60°C

6

18

24

30W

50

12

A1

A2

Ambient Temperature

Fig. 20-7
Mounting
Orientation C
(Table-top
mounting)

Output Power

0

10

20

30

40

60°C

6

18

24

30W

50

12

A1

A2

Ambient Temperature

Fig. 20-8
Mounting
Orientation D
(Horizontal cw)

Power

Supply

OUTPUT

INPUT

Output Power

0

10

20

30

40

60°C

6

18

24

30W

50

12

A1

A2

Ambient Temperature

Fig. 20-9
Mounting
Orientation E
(Horizontal ccw)

Power Supply

OUTPUT

IN

PUT

Output Power

0

10

20

30

40

60°C

6

18

24

30W

50

12

A1

A2

Ambient Temperature

Advertising