Operation on two phases, Use without pe on the input – Rockwell Automation 1606-XLP30EQ Power Supply Reference Manual User Manual

Page 20

Advertising
background image

All parameters are specified at 124V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

20

Rockwell Automation Publication 1606-RM006A-EN-P - January 2014

Bulletin 1606 Switched Mode Power Supplies

2

40V

+10%

max.

Fuse

L2

L1

L3

L

N

PE

Power Supply

AC

DC

internal

fuse

20.8. Operation on Two Phases

The power supply can also be used on two-phases of a three-phase-system. A
phase-to-phase connection is allowed as long as the supplying voltage is
below 240V

+10%

. Use a fuse or a circuit breaker to protect the N input. The N

input is not internally protected and is in this case connected to a hot wire.
Appropriate fuses or circuit breakers are specified in section 20.4.

20.9. Use without PE on the Input

From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2.
Please contact R-A if you decide not to use the PE terminal. A different marking of the front foil will then required.
Grounding of the input is beneficial for a high EMI immunity: symmetrical spikes or fast transients on the input side
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on
the output side caused by the input is much smaller compared to not connecting this terminal to ground.

Fig. 20-3 Grounded input

Fig. 20-4 Ungrounded input

Surge

Y

X

L

N

Ground

Power Supply

+

-

Surge

X

L

N

Power Supply

+

-