Hold-up time, Dc input – Rockwell Automation 1606-XLP30EQ Power Supply Reference Manual User Manual

Page 7

Advertising
background image

All parameters are specified at 124V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM006A-EN-P - January 2014

7

Bulletin 1606 Switched Mode Power Supplies

6. Hold-up Time

AC 100V

AC 120V

AC 230V

Hold-up Time

typ.

41ms

66ms

285ms

at 24V, 0.65A, see Fig. 6-1

typ.

18ms

31ms

141ms

at

24V,

1.3A,

see

Fig.

6-1

Note: At no load, the hold-up time can be up to several seconds. The green DC-on lamp is also on during this time


Fig. 6-1 Hold-up time vs. input voltage

Fig. 6-2 Shut-down behavior, definitions

0

20

40

100

120ms

85

120

155

190

230Vac

Input Voltage

Hold-up Time

60

80

a) 24V 0.65A typ.

b) 24V 0.65Amin.

c) 24V 1.3A typ.

d) 24V 1.3A min.

a

b

c

d

- 5%

Hold-up Time

Zero Transition

Output
Voltage

Input
Voltage



7. DC Input

The power supply can also be supplied from a DC source. Use a battery or similar DC source. For other sources, contact
R-A. Connect the + pole to L and the – pole to N. Connect the PE terminal to an earth wire or to the machine ground.

DC input

nom.

DC 110-300V

-20%/+25%

DC input range

min.

88-375Vdc

continuous operation, reduce output power according
Fig. 7-2 at voltages below 110Vdc

Allowed Voltage L/N to Earth

max.

375Vdc

IEC 62103

DC input current

typ.

0.31A / 0.12A

110Vdc / 300Vdc, at 24V, 1.3A

Turn-on voltage

typ.

60Vdc

steady state value

Shut-down voltage

typ.

35Vdc

steady state value

Fig. 7-1 Wiring for DC Input

Fig. 7-2 Allowable output current below

110Vdc input voltage

+

-

Load

L

N

PE

+

-

Power Supply

AC

DC

Battery

internal

fused

0

5

10

15

20

30W

85

95

105

115

135Vdc

Input Voltage Vdc

Output Power

25

125

(a)

(b)

(a) Ambient <60°C

(b) Ambient <45°C

Advertising