Pc receiver location and connection, Bottlenecks – Rockwell Automation 1425 PowerMonitor Wireless 250 User Manual
Page 19
Rockwell Automation Publication 1425-UM001A-EN-P - January 2012
19
Hardware Installation
Chapter 2
Constricted Topology: Not Recommended
In some cases, PowerMonitor W250 devices might be located far away from the
PC Receiver and all data from the network has to travel over a single path. Such a
situation creates bottlenecks and increases the risk of losing data packets.
We recommend avoiding such topologies by adding additional routers to provide
parallel links to the PC Receiver.
Figure 11 - Constricted Topology
PC Receiver Location and Connection
Consider these suggestions when locating your PC Receiver:
• When possible, locate the PC Receiver near the geographical center of the
RF network.
• It may be helpful to have a notebook personal computer for startup,
diagnostics, and troubleshooting.
Follow these steps to connect the PC Receiver.
1. Apply power to the PC Receiver by plugging in the DC power supply
adapter.
We recommend that you apply power to the PC Receiver prior to applying
power to any PowerMonitor W250 devices.
PM
W250
RTR
RTR
RTR
RTR
PCR
Bottlenecks
PM
W250