Comments on PowerMonitor W250 Modbus Register Tables

The following sections provide comments on the Modbus register tables.

Energy Usage Data (Register 0…23)

These registers contain the raw, unscaled total consumed energy measured by the
PowerMonitor W250 unit. The scaling factors listed in the next section must be
applied to obtain energy values in the applicable engineering units of wH, VARh,
and VAh. The energy counter time-stamp indicates when the data is sent to the
gateway.

Energy usage data increments positive for energy consumed and negative for
energy generated.

Real, reactive, and apparent energy consumption values are stored as 32-bit
integer values using two Modbus registers. The lower register address contains
the high (most significant) word (MSW), the higher register contains the low
(least significant) word value (LSW).

See

Scaling Factors

for information on scaling the raw energy values in these

registers.

Table 15 - Information for

Table 14

Term

Description

Comments

NV

Non-volatile

Value is restored after a power cycle

V

Volatile

Value is not restored after a power cycle

S16

Signed 16-bit INT

Range -32,768…32767

U16

Unsigned 16-bit INT

Range 0…65,535

S32

Signed 32-bit INT

Range -2,147,483,648…2,147,483,647

U32

Unsigned 32-bit INT

Range 0…4,294,967,297

MSW

Most Significant Word

LSW

Least Significant Word

Table 16 - Energy Counters

0, 2, …22

1, 3, …23

MSW LSW