Network identification of powermonitor w250, Modbus communication reference – Rockwell Automation 1425 PowerMonitor Wireless 250 User Manual

Page 49

Advertising
background image

Rockwell Automation Publication 1425-UM001A-EN-P - January 2012

49

Software Interface

Chapter 3

Network Identification of PowerMonitor W250

Each of the PowerMonitor W250 units has a unique 16-bit Device ID, which is
printed on the label in the form of [High Byte].[Low Byte].

The low byte of the Device ID is the device Modbus address.

Modbus Communication Reference

The PowerMonitor W250 units are seen as Modbus slaves through the PC
Receiver. The maximum size of a Modbus RTU frame is 256 bytes. A Modbus
request has the following general format.

Read Holding Registers (Function code 0x03)

The following is a Modbus master read request packet. A request is referred to as
a packet sent from the Modbus master application to the gateway slave. This has a
function code value of 0x03, Read Holding Registers.

The Request Data includes a 2-byte starting address offset value and a 2-byte
length value specifying the length of data to be returned in a 16-bit word
(number of Holding Registers, 1…125 (0x7D).

Examples

Read the frequency from the PowerMonitor W250 with Modbus address 63:

Modbus address - 0x3F
Starting register - 0x1B (register 27 decimal)
Length - 0x01

[3F 03 00 1B 00 01 F0 D3]

Table 27 - Modbus Request Format

Description

Slave Address

Function Code

Request Data

CRC

Byte Count

1

1

4 (typical, see below) 2 (LSB | MSB)

Table 28 - Master Request Format

Description

Slave Address

Function Code

Request Data

CRC

Hex

0xID

0x03

0xXX …0x7D

0xLSB 0xMSB

Table 29 - Slave Request Format

Description

Slave Address

Function Code

Request Data

CRC

Hex

0xID

0x03

0xXX 0xYY

0xLSB 0xMSB