All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

12

Rockwell Automation Publication 1606-RM023A-EN-P — January 2014

Bulletin 1606 Switched Mode Power Supplies

13. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

see Fig. 13-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Humidity

**)

5 to 95% r.H.

IEC 60068-2-30

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis

IEC 60068-2-6

Shock

30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 6000m (0 to 20 000ft)

Reduce output power or ambient temperature
above 2000m sea level.

Altitude de-rating

5.8W/1000m or 5°C/1000m

above 2000m (6500ft), see Fig. 13-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

Altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize while condensation is present

Fig. 13-1 Output current vs. ambient temp.

Fig. 13-2 Output current vs. altitude at 24V

0

-25

0

20

40

70°C

1

2

3

4A

60

Ambient Temperature

Allowable Output
Current

0

0

2000

4000

6000m

1

2

3

4A

Altitude

A... Tamb < 70°C

B... Tamb < 60°C

B

A

Allowable Output
Current

14. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 31Vdc
max. 32Vdc

in case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.

Reverse input polarity protection Included

unit does not start when input voltage is reversed

Output over-current protection

electronically limited

*)

see

Fig.

5-1

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 3.5mm

e.g. screws, small parts

Over-temperature protection

yes

output shut-down with automatic restart

Input transient protection

MOV

Metal Oxide Varistor

Internal input fuse

T10A H.B.C.

not user replaceable

*) In case of a protection event, audible noise may occur.