15. Safety Features

Input / output separation

*)

SELV

IEC/EN

60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

Class of protection

III

PE (Protective Earth) connection not required. A
connection of the “chassis ground” pin to earth is
recommended for best EMI performance

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

between housing and Chassis Ground terminal

Touch current (leakage current)

The leakage current which is produced by the DC/DC converter itself depends on the
input voltage ripple and need to be investigated in the final application.
For a smooth DC input voltage, the produced leakage current is less than 100μA.

*)

Double or reinforced insulation

16. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground.

Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings
to the value in the table below.

Fig. 16-1 Dielectric strength

A B C

Type test

60s

1500Vac

1500Vac 500Vac

Factory test

5s

1500Vac 1500Vac 500Vac

Field test

5s

1000Vac

1000Vac

500Vac

Cut-off current setting

> 30mA

> 30mA

> 12mA

A

C

B

+

Input

Chassis
ground

Output

-

+

-


To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.

17. Environmental Compliance

The unit does not release any silicone and is suitable for the use in paint shops.
The unit conforms to the RoHS directive 2002/96/EC
Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems.
Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated.
The production material within our production does not include following toxic chemicals:
Polychlorized Biphenyl (PCB), Polychlorized Terphenyl (PCT), Pentachlorophenol (PCP), Polychlorinated naphthalene
(PCN), Polybrom Biphenyll (PBB), Polybrom Bipheny-oxyd (PBO), Polybrominated Diphenylether (PBDE), Polychlorinated
Diphenylether (PCDE), Polydibromphenyl Oxyd (PBDO), Cadmium, Asbest, Mercury, Silicia