All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

4

Rockwell Automation Publication 1606-RM023A-EN-P — January 2014

Bulletin 1606 Switched Mode Power Supplies

3. Input Voltage

Input voltage

nom.

DC 24V

Input voltage range

14.4-32.4Vdc

full specified

max.

36.0Vdc

absolute maximum continuous input voltage with no
damage to the DC/DC converter

Allowed voltage between input
and earth

max. 60Vdc

or

42.2Vac

in case the output voltage is not grounded.

Allowed input ripple voltage

max.

5Vpp

47Hz-40kHz, the momentary input voltage must always
be within the specified limits.

Turn-on voltage

typ.

17.5Vdc

steady-state value, see Fig. 3-1

Shut-down voltage

typ.

14.0Vdc

steady-state value, see Fig. 3-1

typ.

35.0Vdc

steady-state

value,

see

Fig.

3-1

Input current

typ.

4.25A

at 24Vdc input and output 24V, 3.8A, see Fig. 3-3

Start-up delay

typ.

290ms

see Fig. 3-2

Rise time

typ.

520ms

0mF, 24V, resistive load 3.8A, see Fig. 3-2

typ.

610ms

3.8mF, 24V, resistive load 3.8A, see Fig. 3-2

Turn-on overshoot

max.

500mV

see Fig. 3-1

Input capacitance

typ.

3 000μF

external capacitors on the input voltage bus are allowed
without any limitations.

Fig. 3-1 Input voltage range

Tur

n

-on

17.

5V

dc

V

IN

P

OUT

S

hut

-down

4V

dc

0V

dc

4V

dc

32.

14. 14.

Rated input range

35.

0V

dc

Fig. 3-2 Turn-on behavior, definitions

Fig. 3-3 Input current vs. output load

Start-up

delay

Rise

Time

Ov

4A

ersh

oot

- 5%

Output
Voltage

Input
Voltage

1

1.5

2

3

0

1

3

5

6A

Output Current

2.5

3.5

0.5

Input Current, typ

Inp

ut:

18

Vd

c

2

4

Inpu

t: 2

4Vd

c

Advertising