All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

14

Rockwell Automation Publication 1606-RM023A-EN-P — January 2014

Bulletin 1606 Switched Mode Power Supplies

Product certification information (including Certificates and Declarations of Conformity) can be found at

www.ab.com/certification

.

18. Certifications

UL 508

LISTED E56639; listed for use in the U.S.A. (UL 508) and Canada
(C22.2 No. 14-95) Industrial Control Equipment

UL 60950-1

RECOGNIZED E168663; recognized for use in the U.S.A. (UL 60950-1)
and Canada (C22.2 No. 60950-1);
Information Technology Equipment, Level 3

GOST R

GOST R certification is applicable for products intended for sale
and use within Russia. See below for link to the certificate.

C-TICK

C-tick compliance is for products intended for sale and use within
the Australian market. See below for the link to the C-tick
Declarations of Conformity.

Marine GL

GL (Germanischer Lloyd) classified for marine and offshore
applications. Environmental category: C, EMC2. See below for link
to the certificate.

Marine Rina

RINA (Registro Italiano Navale) certified. See below for the link to
the certificate.

CSA Certified under File Number 240020

CSA 22.2 No 107,1-01
60950-1

RECOGNIZED UNDER FILE NUMBER E244404 for use in the U.S.A.
(ISA 12.12.01) and Canada (C22.2 No. 213)
Hazardous Location Class I Div 2 - Groups A, B, C, D

ISA 12.12.01, CSA
C22.2 No. 213

ATEX

Approval for use in hazardous locations Zone 2 Category 3G.
Number of ATEX Certificate: EPS 11 ATEX 1 312 X
The redundancy module must be built-in in an IP54 enclosure.

II 3G Ex nA IIC T4 Gc

ATEX

IECEx

IEC 60079-0, IEC 60079-15

IECEx

Suitable for use in Class 1 Zone 2 Groups IIa, IIb and IIc locations.
Number of IECEx certificate: IECEx EPS 14.0008X

EN 60950-1, EN 61204-3

Complies with CE EMC and CE Low Voltage Directives