11. Terminals and Wiring

All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring.

Input Output

Type

screw terminals

screw terminals

Solid wire

0.5-6mm

2

0.5-6mm

2

Stranded wire

0.5-4mm

2

0.5-4mm

2

American Wire Gauge

20-10 AWG

20-10 AWG

Wire stripping length

7mm / 0.275inch

7mm / 0.275inch

Screwdriver

3.5mm slotted or
Pozidrive No 2

3.5mm slotted or
Pozidrive No 2

Recommended tightening torque

1Nm, 9lb.in

1Nm, 9lb.in

Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:

60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.

b) Follow

national installation codes and installation regulations!

c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed.
h) Do not connect or disconnect the wires from the terminals below -25°C (-13°F).

12. Lifetime Expectancy and MTBF

These units are extremely reliable and use only the highest quality materials. The number of critical components such
as electrolytic capacitors has been reduced.

AC 100V

AC 120V

AC 230V

Lifetime expectancy

*)

34 000h

41 000h

56 000h

at 12V, 4.5A and 40°C

122 000h *)

123 000h *)

85 000h *)

at 12V, 2.25A and 40°C

95 000h *)

115 000h *)

158 000h *) at 12V, 4.5A and 25°C

MTBF

**)

SN 29500, IEC 61709

1 183 000h

1 336 000h

1 571 000h

at 12V, 4.5A and 40°C

2 173 000h

2 414 000h

2 786 000h

at 12V, 4.5A and 25°C

MTBF

**)

MIL HDBK 217F

788 000h

835 000h

846 000h

at 12V, 4.5A and 40°C; Ground Benign GB40

1 044 000h

1 111 000h

1 137 000h

at 12V, 4.5A and 25°C; Ground Benign GB25

*) The

Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime

expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.

**)

MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.