Bulletin 1606 Switched Mode Power Supplies

15. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 18Vdc
max. 19Vdc

In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. In such a
case, the output shuts down and stays down until the
input voltage is turned off and on again.

Output over-current protection

electronically limited

see Fig. 5-1

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 2.5mm in diameter

e.g. screws, small parts

Over-temperature protection

not included

Input transient protection

MOV

Metal Oxide Varistor

Internal input fuse

T3.15A H.B.C.

not user replaceable

*) In case of a protection event, audible noise may occur.

16. Safety Features

Input / output separation

*)

SELV

IEC/EN

60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

Class of protection

I

PE (Protective Earth) connection required

II (with restrictions)

for use without PE connection contact PULS

Isolation resistance

> 5MOhm

Input to output, 500Vdc

Touch current (leakage current)

typ. 0.13mA / 0.29mA

100Vac, 50Hz, TN-,TT-mains / IT-mains

typ. 0.19mA / 0.40mA

120Vac, 60Hz, TN-,TT-mains / IT-mains

typ. 0.30mA / 0.63mA

230Vac, 50Hz, TN-,TT-mains / IT-mains

< 0.17mA / 0.38mA

110Vac, 50Hz, TN-,TT-mains / IT-mains

< 0.25mA / 0.53mA

132Vac, 60Hz, TN-,TT-mains / IT-mains

< 0.41mA / 0.85mA

264Vac, 50Hz, TN-,TT-mains / IT-mains

*) Double or reinforced insulation