background image

All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

2

Rockwell Automation Publication 1606-RM016A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

Power Supply

100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efficiency up to 87.6%
Low No-load Losses and Excellent Partial-load Efficiency
Compact Design, Width only 45mm
Electronic Inrush Current Limitation
Operation down to -40°C
Full Output Power up to +60°C
Large International Approval Package

3 Year Warranty

Description

Compact size, light weight, simple installation on the
DIN rail and the integration of the highest quality
components are the factors that make our power
supplies so easy to deploy and use within seconds.

A rugged electrical and mechanical design as well as a
high immunity against electrical disturbances on the
mains provide reliable output power. This power supply

offers superior protection for equipment connected to
the public mains network or exposed to a critical
industrial environment.

and a power rating from 15W to 120W.

The 1606-XLP60BQT is specially designed for electronic
inrush current limitation and is suitable for very low
ambient temperatures.
The unit is fully specified down to -40°C.

Optionally, you may use a supplementary decoupling diode
module to build redundant systems or to protect your
installation against back-feeding voltages.

Specification Quick Reference

Output voltage

DC 12V

Adjustment range

12 - 15V

Output current

4.5A at 12V
3.6A at 15V

Output power

54W

Output ripple

< 50mVpp

20Hz to 20MHz

Input voltage

AC 100-240V

-15% / +10%
AC 100V mains
requires derating

Mains frequency

50-60Hz

±6%

AC Input current

0.97 / 0.61A

at 120 / 230Vac

Power factor

0.54 / 0.44

at 120 / 230Vac

AC Inrush current

typ. 6A

input voltage
and temperature
independent

DC Input

88-375Vdc

below 130Vdc
derating required

Efficiency

85.8 / 87.6%

at 120 / 230Vac

Losses

8.9 / 7.6W

at 120 / 230Vac

Temperature range -40°C to +70°C

operational

Derating 1.4W/°C

+60

to

+70°C

Hold-up time

typ. 25 / 113ms

at 120 / 230Vac

Dimensions 45x75x91mm

WxHxD

Weight 250g

/

0.55lb

Catalog Numbers

Power Supply

1606-XLP60BQT 12-15V Standard unit


Certification Marks

Ind. Cont. Eq. UL 508

UL 60950-1

Marine

NEC

Class 2

EMC, LVD, RoHS

The XLP family offers output voltages from 5 to 56Vdc

Marine RINA

GOST R

C-Tick