Cable Adjustment Procedure
1
Move handle to “ON” position.
2
Remove cable pivot hitch pin and washer.
3
Push cable pivot out of handle bracket.
4
Return handle to “OFF” position.
5
(a) ADJUSTMENT PROCEDURE IF
SWITCH DOES NOT FULLY CLOSE
Unscrew cable pivot ONE full turn
counter-clockwise to extend cable.
5
6
Return handle to “ON” position and insert
cable pivot back into mechanism.
7
Re-install cable pivot washer and hitch pin.
8
Confirm switch operates properly and
repeat steps 5-7 if necessary.