(7)

PN-224754
DIR 10001182729 (Version 01)

Cable Adjustment Procedure

1

Move handle to “ON” position.

2

Remove cable pivot hitch pin and washer.

3

Push cable pivot out of handle bracket.

4

Return handle to “OFF” position.

5

(a) ADJUSTMENT PROCEDURE IF
SWITCH DOES NOT FULLY CLOSE
Unscrew cable pivot ONE full turn
counter-clockwise to extend cable.

5

6

Return handle to “ON” position and insert
cable pivot back into mechanism.

7

Re-install cable pivot washer and hitch pin.

8

Confirm switch operates properly and
repeat steps 5-7 if necessary.

(b) ADJUSTMENT PROCEDURE IF
SWITCH DOES NOT FULLY OPEN
Turn cable pivot ONE full turn
clockwise to shorten cable.