Bulletin 1608S i-Sense® Installation Instructions

Installation

Pre-installation

1.

Inspect for shipping damage

2.

Record the i-Sense® serial number *

3.

Register the i-Sense at www.igrid.com*

4.

Configure the i-Sense hardware for the service voltage *

5.

Configure communications software using the Ethernet port. (this can be
done after installation and power-up)

* For more information, please refer to Rockwell Automation Publication 1608S-UM001-EN-P

WARNING: Do not apply power to the i-Sense until the wiring is completed
and right-side cover is replaced. Installation must be performed by an
electrician, in accordance with all local and national codes.

Environmental Conditions

The i-Sense is rated for installation in the following environment:

Indoor use only, no conductive pollution.

Altitude up to 2000 m (6500 ft)

Temperature range +0...+40 °C (+32...+104 °F)

Maximum relative humidity 95%, non-condensing.

Mounting

Provide 10 inches (250 mm) clearance around the i-Sense for cooling and
access.

Remove the left and right covers (four Phillips-head screws, two top and
two bottom)

Mount the i-Sense to a vertical surface using the four mounting holes. Two
of the four mounting screws should penetrate into studs at least 1 in.
(25 mm). Mounting screws 1.5 in. (38 mm) long are recommended.

Electrical Connections

Branch protection: upstream fuse or circuit breaker protection rated 20A
or less is required. Protection rated less than 5 A is not recommended.

Conduit entry: top or bottom.

Connect the Ground (Earth) wire to the #10-32 stud near the bottom
knock-out.

Connect mains line to the INPUT_1 terminal block, according to the
proper wiring diagram from

Table 1

.

6-Channel Version: if the INPUT_2 terminal block is present, wire the
second 3-phase set using the same wiring diagram.

Verify that the JP1 plug is properly configured, per

Table 2

: The plug with

RED wires must be installed if the channel voltage is greater than 250
VAC.

Replace the right-side cover and two screws

WARNING: This unit is not rated for 600V AC or 690V AC L-L installations.

600Y/346V installations require 4-wire L-N wiring method. The neutral must be
connected as shown in

Table 1

.