Technical specifications – Rockwell Automation 1608S I-Sense Installation Instructions User Manual

Page 7

Advertising
background image

Rockwell Automation Publication 1608S-IN001A-EN-P - July 2013

7

Bulletin 1608S i-Sense® Installation Instructions

Technical Specifications

Electrical

Nominal Voltage

User-selectable, 100V-480Vrms, 1-Phase or 3-Phase Immune to voltage
fluctuation up to ±10% of nominal and transient over voltages typically present
on mains supply (impulse withstand Category II of IEC 60364-4-443)

Frequency

45...65 Hz, auto-sensing

Measurement inputs

1 to 3 channels, Cat. No.: 1068S-3V480K (3-channel)
Up to 6 channels, Cat. No.: 1068S-6V480K (6-channel)

RMS voltage measurement accuracy

0.2% typical, ± 2% maximum (of full-scale)
True rms

Sample rate

5760 sample/second

Waveform capture rate

32 samples/cycle

Time Stamp

±0.1 seconds typical accuracy
Real-time clock synchronized to UTC (NIST standard) daily, via

i-Grid and SNTP protocol

Data Storage

Non-volatile event storage > 300 events

Memory cleared after automatic up load to i-Grid.

Voltage Deviation Event detection trigger.

1/2-cycle rms voltage ≤ 87% or ≥115% of set nominal

Adaptive waveform deviation detection of transient events.

Voltage Deviation Event Storage

8 cycles waveform data (-1...+3 cycles at event start and -3...+1 cycles at the
event end) Continuous rms voltage trend, up to 2 minutes.

Periodic (PRMS) Data Logging

Minimum, Maximum and Average rms voltage recorded for each 10-minute
period. Min./Max. are lowest/highest sliding 1/2 -cycle rms period

Power supply and battery backup

Powered from Channel 1 (L1-L2 or L1-N), < 25VA load
9VDC external power supply (not provided - for configuration only)
Rechargeable batteries enable measurement & communications during power
interruptions for up to 2 minutes

Mechanical & Environmental

Enclosure

NEMA 1 (IP20). Indoor use only.

Only non-conducting pollution (degree II)

Dimensions: 11.4” H x 9.7” W x 3.0” D (291 mm H x 247 mm W x 75 mm D)

Weight

8.5 lb (3.6 kg)

Operating Temperature

0...+ 40 °C (+32...+104 °F)

Storage Temperature

-40...+ 75 °C (-40...167 °F)

Relative Humidity

0...95%, non-condensing

Altitude 2000 m

(6,562 ft) at +40 °C

Communications

Internet Communications

Over port 80 via HTTP protocol. Outgoing only.

Ethernet

IEEE 802.3 10 Base-T (10 Mb/s), 8P8C (RJ45) modular connector

Modem (optional)

PSTN (analog telephone) RJ11 modular connector, Most global phone systems
supported

Indicators

Red and green front-panel LEDs

i-Sense Management Console

On-board Web server for configuration and status, password protected.