Rockwell Automation Publication 1608S-IN001A-EN-P - July 2013

5

Bulletin 1608S i-Sense® Installation Instructions

Nominal Voltage
Configurations

Table 2 - Nominal Voltage Configurations. (shipped standard with 480V (L-L)

Your Voltage

Nominal
Volts per
Channel

Channels

Mains
Wires

Wiring
Diagram
(See Table 2)

Power Supply
Jumper JP1

Any single-phase voltage ≤240V

nominal

1

2

S1

White wires

100 (L-N for 100/200V split-phase)

100

2

3

S2

White wires

105 (L-N for 105/210V split-phase)

105

2

3

S2

White wires

110 (L-N for 190Y/110V 3-phase)

110

3

4

LN

White wires

115 (L-N for 200Y/115V 3-phase)

115

3

4

LN

White wires

115 (L-N for 115/230V split-phase)

115

2

3

S2

White wires

120 (L-N for 208Y/120V 3-phase)

120

3

4

LN

White wires

120 (L-N for 120/240V split-phase)

120

2

3

S2

White wires

125 (L-N for 216Y/125V 3-phase)

125

3

4

LN

White wires

127 (L-N for 220Y/127V 3-phase)

127

3

4

LN

White wires

133 (L-N for 230Y/133V 3-phase)

133

3

4

LN

White wires

139 (L-N for 240Y/139V 3-phase)

139

3

4

LN

White wires

190 (L-L for 190Y/110V 3-phase)

190

3

3

LL

White wires

200 (L-L for 100/200V split-phase)

200

1

2

S1

White wires

208 (L-L for 208Y/120V 3-phase)

208

3

3

LL

White wires

210 (L-L for 105/210V split-phase)

210

1

2

S1

White wires

216 (L-L for 216Y/125V 3-phase)

216

3

3

LL

White wires

220 (L-L for 380Y/220V 3-phase)

220

3

3

LL

White wires

230 (L-L for 230Y/133V 3-phase)

230

3

3

LL

White wires

230 (L-N for 400Y/230V 3-phase)

230

3

4

LN

White wires

240 (L-L for 120/240V split-phase)

240

3

3

LL

White wires

240 (L-N for 415Y/240V 3-phase)

240

3

4

LN

White wires

254* (L-N for 440Y/254V 3-phase)

254

3

4

LN

Red wires

277 (L-N for 480Y/277V 3-phase)

277

3

4

LN

Red wires

346 (L-N for 600Y/346V 3-phase)

346

3

4

LN

Red wires

346 (L-L for 346Y/200V 3-phase)

346

3

3

LL

Red wires

380 (L-L for 380Y/220V 3-phase)

380

3

3

LL

Red wires

400 (L-L for 400Y/230V 3-phase)

400

3

3

LL

Red wires

400 (L-N for 690Y/400V 3-phase)

400

3

4

LN

Red wires

415 (L-L for 415Y/240V 3-phase)

415

3

3

LL

Red wires

440 (L-L for 440Y/254V 3-phase)

440

3

3

LL

Red wires

440 (L-L for 220/440V split-phase)

440

3

3

LL

Red wires

460 (L-L, at point of use)

460

3

3

LL

Red wires

480 (L-L for 480Y/277V 3-phase)

480

3

3

LL

Red wires

600 (L-L 3-phase) not allowed

No

No

No

No

No

690 (L-L 3-phase) not allowed

No

No

No

No

No

* Nominal 254V source must operate normally at > 240V (95% of nominal)

** Maximum 480V per channel. 575Y/332V and 600Y/346V systems must use the 346 (L-N) configuration. 690Y/400V
systems must use the 346 (L-N) configuration.