Table 1 - wiring diagrams, Table 1, Important – Rockwell Automation 1608S I-Sense Installation Instructions User Manual

Page 4

Advertising
background image

4

Rockwell Automation Publication 1608S-IN001A-EN-P - July 2013

Bulletin 1608S i-Sense® Installation Instructions

1.

Select your voltage
configuration from

Table 2

and

follow the instructions in the
corresponding wiring diagram
from

Table 1

.

2.

Use the appropriate wiring
diagram and jumper wire
positions. The i-Sense is
shipped with jumper wires in
the LL configuration. The LL
and LN diagrams are also
shown inside the i-Sense cover.
Move or remove jumper wires
as needed.

Table 1 - Wiring Diagrams

IMPORTANT

There should be no more than one wire installed at each terminal block position
Maximum 480V per channel
575Y/332V and 600Y/364V systems must use the 346 (L-N) configuration
690Y/400V systems must use the 400 (L-N) configuration

IMPORTANT

See i-Sense Management Console to set the nominal voltage.

NORMAL

ERROR

L
e
f
t

C
o
v
e
r

R
i
g
h
t

C
o
v
e
r

1 2 3 4 5 6

7 8 9

L1

L2

L3

3 channel sensing
3 wires + ground required
Jumper pins 1-6 & 3-7 & 4-9
Use AWG 14-22(.34-2.5 mm

²)

, 600V AC conductors

Tighten screws to 12-13 lb-in (1.4 Nm)
Tighten ground stud nut to 30 lb-in (3.4 Nm)
The ground stud is #10-32.

GND

LL

3-Phase 3-wire

Source type

Wiring Diagram

1

2 3 4 5 6 7 8 9

L1

L2

N

1

2 3 4 5 6 7 8 9

L1 (N or L2)

1 channel sensing
2 wires + ground required
No jumper wires
Use AWG 14-22 (.34-2.5 mm

²)

, 600V AC conductors

Tighten screws to 12-13 lb-in (1.4 Nm)
Tighten ground stud nut to 30 lb-in (3.4 Nm)
The ground stud is #10-32.

2 channel sensing
3 wires + ground required
Jumper pins 3-5
Use AWG 14-22(.34-2.5 mm

²)

, 600 VAC conductors

Tighten screws to 12-13 lb-in (1.4 Nm)
Tighten ground stud nut to 30 lb-in (3.4 Nm)
The ground stud is #10-32.

GND

GND

S2

Split-phase

S1

Single phase

1

2 3 4 5 6 7 8 9

L1

L2

L3

N

3 channel sensing
4 wires + ground required
Jumper pins 3-5 & 6-8
Use AWG 14-22(.34-2.5 mm

²)

, 600V AC conductors

Tighten screws to 12-13 lb-in (1.4 Nm)
Tighten ground stud nut to 30 lb-in (3.4 Nm)
The ground stud is #10-32.

GND

LN

3-Phase 4-wire

Advertising