Rockwell Automation 1606-XLS960E-3 Power Supply Reference Manual User Manual

Page 15

Advertising
background image

All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

15

Bulletin 1606 Switched Mode Power Supplies

17. EMC

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. A detailed EMC report is available on request.

EMC Immunity

According generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

contact discharge
air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

input lines
output lines
DC-OK signal (coupling clamp)

4kV
2kV
2kV

Criterion A
Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

L1 L2, L2 L3, L1 L3
L1 / L2 / L3 PE

2kV
4kV

Criterion A
Criterion A

Surge voltage on output

EN 61000-4-5

+ -
+ / - PE

1kV
1kV

Criterion A
Criterion A

Surge voltage on DC-OK

EN 61000-4-5

DC-OK signal PE

1kV

Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

Mains voltage dips
(Dips on three phases)

EN 61000-4-11

0% of 380Vac (0Vac)
0% of 480Vac (0Vac)

0Vac, 20ms
0Vac, 20ms

Criterion A,
Criterion A

Mains voltage dips
(Dips on two phases)

EN 61000-4-11

40% of 380Vac (152Vac)
40% of 480Vac (192Vac)
70% of 380Vac (266Vac)
70% of 480Vac (336Vac)

200ms
200ms
500ms
500ms

Criterion A
Criterion A
Criterion A
Criterion A

Voltage interruptions

EN 61000-4-11

0Vac

5000ms

Criterion C

Voltage sags

SEMI F47 0706

dips on two phases according to section 7.2. of the SEMI F47 standard

80% of 380Vac (304Vac)
70% of 380Vac (266Vac)

50% of 380Vac (160Vac)

1000ms
500ms
200ms

Criterion A
Criterion A
Criterion A

Powerful transients

VDE 0160

over entire load range

1550V, 1.3ms

Criterion A

Criteria:

A:

Power supply shows normal operation behavior within the defined limits.

C:

Temporary loss of function is possible. Power supply may shut-down and restarts by itself. The power supply will incur neither damage

nor hazard.

EMC Emission

According generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission
input lines

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B

Conducted emission
output lines

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

5dB higher than average limits
for DC power port according EN
61000-6-3

**)

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

fulfilled for class A equipment

Voltage fluctuations, flicker EN 61000-3-3

fulfilled

*)

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

*)

Tested with constant current loads, non pulsing

**) Restrictions apply for applications in residential, commercial and light-industrial environments, where local DC power networks according

to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications.

Advertising