Hold-up time – Rockwell Automation 1606-XLS960E-3 Power Supply Reference Manual User Manual

Page 8

Advertising
background image

All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

8

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

7. Hold-up Time

3AC 400V

*)

3AC 480V

*)

Hold-up Time

typ.

50ms

50ms

at 24V, 20A, see Fig. 7-1

min.

40ms

40ms

at

24V,

20A,

see

Fig.

7-1

typ.

25ms

25ms

at

24V,

40A,

see

Fig.

7-1

min.

20ms

20ms

at 24V, 40A, see Fig. 7-1

*)

Curves and figures for operation on only 2 legs of a 3-phase system can be found in section 25-4.

Fig. 7-1 Hold-up time vs. input voltage

Fig. 7-2 Shut-down behavior, definitions

0

10

20

30

40

50ms

320

360

400

440

3x480Vac

Input Voltage

Hold-up Time

24V, 20A, typ.

24V, 40A, typ.

24V, 20A, min.

24V, 40A, min.

- 5%

Hold-up Time

Output
Voltage

Input
Voltage

L1 L2 L3