All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

16

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

Switching Frequencies

The power supply has three converters with three different switching frequencies
included. One is nearly constant. The others are variable.

Switching frequency 1

105kHz

Resonant converter, nearly constant

Switching frequency 2

1kHz to 150kHz

Boost converter, load dependent

Switching frequency 3

40kHz to 300kHz

PFC converter, input voltage and load dependent


18. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

reduce output power according Fig. 18-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Output de-rating

24W/°C

60-70°C (140°F to 158°F)

Humidity

**)

5 to 95% r.H.

IEC 60068-2-30

Vibration, sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g

***)

2 hours / axis

IEC 60068-2-6

Shock

15g 6ms, 10g 11ms

***)

3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 2000m (0 to 6 560ft)

no restrictions

2000 to 6000m (6 560 to 20 000ft)

reduce output power or ambient temperature,
see Fig. 18-2
IEC 62103, EN 50178, overvoltage category II

Altitude de-rating

60W/1000m or 5°C/1000m

> 2000m (6500ft), see Fig. 18-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

LABS compatibility

The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.

*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. Curves and

figures for operation on only 2 legs of a 3-phase system can be found in section 25.4.

**) Do not energize in the presence of condensation.
***) Higher levels allowed when using the 1606-XLC wall mounting bracket.

Fig. 18-1 Output current vs. ambient temp.

Fig. 18-2 Output current vs. altitude

Allowed Output Current at 24V

0

-25

0

20

40

70°C

10

20

30

40

50

60A

continuous

60

Ambient Temperature

short-term (4s)

Allowed Output Current at 24V

0

0

2000

4000

10

20

30

40

50

60A

continuous

6000m

Altitude

short-term (4s)

A

C

A... Tamb < 60°C

B... Tamb < 50°C

C... Tamb < 40°C

B