All parameters are specified at 24V, 40A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM005A-EN-P - February 2014

17

Bulletin 1606 Switched Mode Power Supplies

19. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 30Vdc
max. 32Vdc

In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 5mm

e.g. screws, small parts

Over-temperature protection

yes

Output shut-down with automatic restart

Input transient protection

MOV (Metal Oxide Varistor)

Internal input fuse

included

not user replaceable

*) In case of a protection event, audible noise may occur.



20. Safety Features

Input / output separation

*)

SELV

IEC/EN

60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

double or reinforced insulation

Class of protection

I

PE (Protective Earth) connection required

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

Touch current (leakage current)

typ. 0.35mA / 0.64mA

3x400Vac, 50Hz, TN-,TT-mains / IT-mains

typ. 0.45mA / 0.91mA

3x480Vac, 60Hz, TN-,TT-mains / IT-mains

max. 0.45mA / 0.78mA

3x440Vac, 50Hz, TN-,TT-mains / IT-mains

max. 0.60mA / 1.20mA

3x528Vac, 60Hz, TN-,TT-mains / IT-mains

*) double or reinforced insulation