User Configurable Items

User Configurable Items

Settings are adjusted through PowerChute

software or optional network management card.

Function

Factory Default

User Selectable Choices

Description

Automatic

Self-Test

Every 14 days

(336 hours)

• Every 7 days

(168 hours)

• On start-up only
• No self-test

Set the interval at which the UPS will execute a

self-test.

UPS ID

UPS_IDEN

Up to eight characters
(alphanumeric)

Uniquely identify the UPS (i.e. server name or
location) for network management purposes.

Date of Last

Battery
Replacement

Manufacture

Date

mm/dd/yy

Reset this date when you replace the battery

module.

Minimum Capacity

Before Return from
Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which battery

module(s) will be charged following a low
battery shutdown before powering connected
equipment.

Voltage Sensitivity

High sensitivity

High sensitivity
Medium sensitivity
Low sensitivity

The UPS detects and reacts to line voltage
distortions by transferring to battery operation
to protect the connected equipment.
In situations of poor power quality, the UPS

may frequently transfer to battery operation. If
the connected equipment can operate normally
under such conditions, reduce the sensitivity
setting to conserve battery capacity and service

life.

Alarm Delay
Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms
permanently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS
receives a shutdown command and actual

shutdown.

Low Battery

Warning

2 minutes

2, 5, 8, 11, 14,

17, 20, 23 minutes

PowerChute software interface provides

automatic, unattended shutdown when
approximately two minutes of battery operated
run time remains.
The low-battery warning beeps are continuous

when two minutes of run time remain.
Change the low battery warning interval setting
to the time that the operating system or system
software requires to safely shut down.