Rockwell Automation 1609-S350NS_ES Uninterruptible Power Supply - 350VA User Manual

Page 8

Advertising
background image

9

User Configurable Items

Synchronized
Turn-on Delay

0 seconds

• 0 s
• 60 s
• 120 s
• 180 s

• 240 s
• 300 s
• 360 s
• 420 s

Specify the time the UPS will wait after the
return of utility power before start-up (to avoid
branch circuit overload).

High Transfer Point

120 V models:
127 VAC

230 V models:

253 VAC

• 127 VAC
• 130 VAC

• 253 VAC
• 257 VAC

• 133 VAC
• 136 VAC

• 261 VAC
• 265 VAC

To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high

transfer point higher if the connected
equipment can tolerate this condition.

Low Transfer Point

120 V models:
106 VAC

230 V models:

208 VAC

• 97 VAC
• 100 VAC

• 196 VAC
• 200 VAC

• 103 VAC
• 106 VAC

• 204 VAC
• 208 VAC

To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low

transfer point lower if the connected equipment
can tolerate this condition.
The 1609-S350ES ships ready for 230 V
sources. When operating the UPS in 208 V

applications, the UPS low transfer voltage
settings are adjusted through PowerChute
software. The proper setting for low transfer

voltage is 196 V.
Refer to the PowerChute user guide for setting
adjustment details.

Output Voltage
230 V models only

230 VAC

• 220 VAC
• 230 VAC

• 240 VAC

Sets the output voltage of the UPS while
operating on battery.

Function

Factory Default

User Selectable Choices

Description