DF1 Messaging with a 1746-BAS Module Example

(Write 10 Parameters then read 10 parameters)

10

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

20

REM

30

REM This file is a program for the 1746–BAS module.

40

REM

50

REM It performs a PLC2 Unprotected Write (08) followed by

60

REM a PLC2 Unprotected Read (01) over the DF1 link on port #2

70

REM

80

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

90

STOP

100

STRING 0,0

110

STRING 512,127

120

$(1)=”THIS IS A TEST! ”

130

REM

140

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

150

REM Setup port 1 to 9600 baud, no parity, 8 bits, 1 stop bit,

160

REM software handshaking, and battery backed ram data storage.

170

REM !!!!REMEMBER TO SET TERMINAL TO MATCH!!!!

180

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

190

MODE (PRT1,9600,N,8,1,S,R)

200

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

210

REM

220

REM Setup port 2 to 300 baud, no parity, 8 bits, 1 stop bit,

230

REM software handshaking, and battery backed ram data storage.

240

REM

250

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

260

MODE (PRT2,300,N,8,1,S,R)

270

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

280

REM

290

REM Enable DF1 driver

300

REM (20 = Setup for Full Duplex, Auto–Detect Embedded Responses,

310

REM Disable Duplicate Packet Detection, BCC error checking)

320

REM (200 = Wait 1 second for polling by Master)

330

REM (2 = 2 retries)

340

REM (0= No RTS on delay)

350

REM (0 = No RTS off delay)

360

REM (8 = 1746–BAS module address)

370

REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

380

PUSH 20

390

PUSH 200

400

PUSH 2

410

PUSH 0

420

PUSH 0

430

PUSH 8

440

CALL 108

450

REM DF1 PLC REMOTE WRITE COMMAND

460

PUSH 2 : REM PLC2 Unprotected Write

470

PUSH 1 : REM Communications Module Node Address

480

PUSH 11 : REM File Number (ignored in this example)

490

PUSH ASC(N) : REM Communications Module File Type

500

PUSH 623 : REM Starting Word in File

510

PUSH 10 : REM Number of Words to Transfer

520

PUSH 50 : REM Command Time–out (x100ms)