7 - specifications, Chapter objectives, Product specifications – Rockwell Automation 1203 Serial Communications Module Series A User Manual

Page 51: Module compatibility, Specifications

Advertising
background image

7

Chapter

7-1

Specifications

Chapter Objectives

The purpose of this chapter is to provide you with background information
and specifications that may be necessary when installing or applying your
Communications Module.

Product Specifications

Open Style

Enclosed Style 115/230V AC

Enclosed Style 24V DC

Catalog Number:

-GM2

–GD2

–GK2

Environmental:

Operating Temperature

0 to 50

_C (32 to 122_F)

0 to 50

_C (32 to 122_F)

0 to 50

_C (32 to 122_F)

Storage Temperature

–40 to 85

_C (–40 to 185_F)

–40 to 85

_C (–40 to 185_F)

–40 to 85

_C (–40 to 185_F)

Relative Humidity

0 to 95%, Non-condensing

0 to 95%, Non-condensing

0 to 95%, Non-condensing

Electrical:

Input Voltage

Supplied by drive

85 to 264V AC, 1-phase

24V DC, +/– 10%

Input Frequency

NA

45 to 63 Hz

NA

Input Current

NA

35mA maximum

0.4 amps maximum

SCANport Load

60mA DC

60mA DC

60mA DC

Communications:

SCANport Side

SCANport Peripheral

Interface

SCANport Peripheral

Interface

SCANport Peripheral

Interface

Serial Side

RS-232/RS422/RS485 (DF1)

RS232/RS422/RS485 (DF1)

RS232/RS422/RS485 (DF1)

Baud Rates

110, 300, 600, 1200, 2400,

4800, 9600, 19.2K

110, 300, 600, 1200, 2400,

4800, 9600, 19.2K

110, 300, 600, 1200, 2400,

4800, 9600, 19.2K

Checksum

BCC or CRC

BCC or CRC

BCC or CRC

Dimensions:

Open (IP00)

NEMA Type 1 (IP30)

NEMA Type 1 (IP30)

NA

45w x 76h x 123d mm

(1.8 x 3.0 x 4.8 in.)

45w x 76h x 123d mm

(1.8 x 3.0 x 4.8 in.)

Module Compatibility

This module is intended for use with devices that communicate via RS232,
RS422, or RS485 hardware standards using the DF1 protocol. It is intended
to provide a means for transmitting messages between these serial-
communications devices and Allen-Bradley SCANport devices.