Maintenance

Preventative Maintenance

The MegaDySC requires very little preventative maintenance. The MegaDySC
should be checked periodically for proper air flow and status indicator operation.

Monthly Checks

Ensure the touch screen display is working and no active events are
displayed.

Check that the Automatic Bypass switchboard is in the MegaDySC
Normal mode.

Update system time, if needed, see

Figure 8 on page 25

.

Clean the display screen if needed. See page

33

.

Ensure air intake and exhaust filters are not covered or obstructed.

3-6 Month Checks

Check air filters and clean when necessary.

Air filters for the MegaDySC will require periodic cleaning, with the
frequency depending on the environment.

Filters are located on the doors of each MegaDySC and ER cabinet, and
can be accessed with the doors closed.

The MegaDySC need not have power removed for this operation.

Remove the grill covers by unscrewing the knurled nuts; the washable
foam filter pads are behind the grill cover.

Replace or gently wash the foam filter pads as needed with a light non-
abrasive soap and water mixture. Towel-dry; do not wring-out.

Place the filter and grill cover back into their location and re-install the
knurled nuts until finger tight.

Replace filters if damaged.

Consult Rockwell Automation technical support for replacement
filters.

Replacement filters must be no more restrictive to air flow than the
original equipment filters.

Check fan for proper operation.

Refer to the Hardware Service Manual for fan test instructions.