Adjustments for 400 amp equipment, Chapter – Rockwell Automation 1503 OEM Starter Frame Components Installation Manual User Manual

Page 35

Advertising
background image

Chapter

3

Adjustments for 400 Amp Equipment

Door Interlock Circumvention

To ensure proper functioning of the isolation switch as-

sembly, perform the following adjustments in the order

they are presented.

The door interlock mechanism is designed to prevent

access to the medium voltage cell while the unit

is energized. When the unit is in operation, do not

circumvent this interlocking safety feature. Always

disconnect and lock out incoming power (see Power

Lock-out Procedure, pg 3-2) before proceeding with any

adjustments requiring the handle to be moved to the ON

(closed) position. Failure to do so may result in electric

shock causing severe burns, injury or death.

Some of the following sections may require moving the isolation switch

handle to the ON position while the medium voltage door is open. The

interlocking safeguards in the mechanism are designed to prevent the

handle from moving to the ON position while the cabinet door is open.

To circumvent this safety feature, use a screwdriver, or other tool, to

depress the door interlock defeater lever in the switch.

Hold the lever down while moving the handle to the ON (closed) posi-

tion.

Interlock Defeater

Lever

Figure 3.1 – Door Interlock Defeater Lever

1503-IN050D-EN-P – June 2012

I M P O R T A N T

I M P O R T A N T

A T T E N T I O N

A T T E N T I O N