Led indicators – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Installation Instructions, PRIOR to Firmware rev. 3.0 User Manual

Page 11

Advertising
background image

Publication 1404-IN007D-EN-P - October 2004

Powermonitor 3000 11

The Display Module is shipped with a 3-meter (10 ft) long, shielded
4-pair cable that provides power and serial communications between
the Master Module and the Display Module. The Display Module fits
into a standard ANSI four inch analog meter cutout for panel
mounting. Only one Display Module may be connected to a Master
Module, although you may use one Display Module to configure and
monitor any number of Master Modules; one at a time.

Figure 4 Display Module

LED Indicators

The Powermonitor 3000 is equipped with six bi-color light emitting
diodes (LED’s) arranged as shown in Figure 5.

Figure 5 LED Indicators

The three LED’s on the left display the same information on
Powermonitor 3000 modules with any communication option
including native RS-485 communications only. The three LED’s on the
right have different labels and different indications depending on the
communications option selected, as shown in the charts below.

Powermonitor 3000

RX

TX

RS-485

MODULE
STATUS

Table 6 LED Indicators All Powermonitor 3000 Models

LED

LED Color

LED State and Communications
Condition

Module Status

Off

Control power is off or insufficient

Steady Red

Major fault; internal self-test has failed. If a
power cycle does not correct the problem,
call customer support

Steady Green

Powermonitor 3000 is operating normally

RS-485 RX

Off

The RS-485 bus is idle; no active data is
present

Flashing Green

Active data is present on the RS-485 bus

RS-485 TX

Off

Powermonitor 3000 is not transmitting data
onto the RS-485 bus

Flashing Green

Powermonitor 3000 is transmitting data
onto the RS-485 bus

Advertising