Dimension Drawings

Figure 41 Master Module Dimensions

Figure 42 Master Module Spacing

203.2 (8.000)

Used With -232

Communications

Options

Powermonitor 3000

14.66

(0.577)

114.30

(4.50)

85.0

(3.346)

Mounting

4.57 (0.180)

4 Places

10.43

(0.411)

5.35

(0.211)

125.0

(4.921)

Mounting

114.30

(4.50)

135.15

(5.321)

184.15 (7.250)

Used With

Display Module

163.17 (6.424)

Used Without

Display Module

5.60

(0.22)

All dimensions are in mm (inches).

Powermonitor 3000

Powermonitor 3000

Powermonitor 3000

Powermonitor 3000

50.8

(2.00)

50.8

(2.00)

50.8 (2.00)

Minimum

(See Note 3)

50.8 (2.00)

Minimum

(See Note 3)

101.6 (4.00)

(See Note 2)

101.6 (4.00)

(See Note 2)

215.9 (8.50)

(See Note 1)

215.9 (8.50)

(See Note 1)

General Notes:
1. Recommended spacing provides

reasonable wiring clearance and ventilation.

2. Maintain approximately 102 mm (4.00 in.) clearance

between master modules and other electrical
equipment.

3. Do not block cooling vents. Wiring and other

obstructions must be 50 mm (2.00 in.) minimum
from top and bottom of unit.

4. Mount with ventilation openings in top and bottom

to provide optimum free convection cooling.

5. Refer to Specifications for ambient temperature

requirements.