Technical specifications, Ansi/ieee tested, Measurement accuracy and range – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 Installation Instructions, PRIOR to Firmware rev. 3.0 User Manual

Page 59: General input, output, and environmental ratings

Advertising
background image

Publication 1404-IN007D-EN-P - October 2004

Powermonitor 3000 59

ANSI/IEEE Tested

Meets or exceeds the Surge Withstand Capability (SWC) C37.90.1 -
1989 for protective relays and relay systems on all power connection
circuit terminations.

Technical Specifications

Measurement Accuracy and Range

See table below for the rating of each parameter

General Input, Output, and Environmental Ratings

Table 43 Measurement Accuracy and Range

Parameter

Accuracy in % of Full Scale at +25°C 50/60 Hz Unity Power Facator

Nominal/Range

M4

M5

M6

M8

Voltage Sense Inputs: V1, V2,
V3

±0.2%

±0.05%

±0.05%

±0.05%

347V/15 to 399V

L-N

RMS

600V/26 to 691V

L-L

RMS

Current Sense Input: I1, I2, I3,
I4

±0.2%

±0.05%

±0.05%

±0.05%

5A/50 mA – 10.6A
RMS

Frequency

±0.05 Hz

±0.05 Hz

±0.05 Hz

±0.05 Hz

50 or 60 Hz/40 to 75 Hz

Power Functions: kW, kVA,
kVAR

Demand Functions: kW, kVA

Energy Functions: kWH, kVAH

ANSI C12.16 and

EN 61036 Class 1
Accuracy

ANSI C12.20 and

EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)

ANSI C12.20 and

EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)

ANSI C12.20 and

EN 60687 Class
0.5 Accuracy
(Class 0.2 is also
available)

Metering Update Rates

55 to 80 ms

45 to 70 ms

45 to 75 ms

40to 90 ms

Table 44 Input and Output Ratings

Control Power

1404-xxxxA-xxx

102V-264V ac 47-63 Hz or

106V-275V dc

(0.2 Amp maximum loading)

1404-xxxxB-xxx

18V to 50V dc (15 VA maximum loading)

Voltage Sense
Inputs: V1, V2, V3

Input Impedance: 1M ohm minimum, 399V ac maximum; V1, V2 and
V3 to N.