Hardwire UPS

Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.

Selection of Cables:

AC Main Input / Output Wiring for UPS:

DC Input / Output Wiring for External Battery Cabinet:

Connect Power and Equipment to the UPS

1. Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see

Diagram 2).

2. Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see

Diagram 2).
Diagram 2 - System Wiring

3. Connect any additional optional accessories (1609-ENET card).

Item

Specification

Wire size

14 AWG

Minimum temperature

75°C

Wire conductor material

Copper only

Tightening torque for terminals

4.4 lb-in

Item

Specification

Wire size

10 AWG

Minimum temperature

75°C

Wire conductor material

Copper only

Tightening torque for terminals

12 lb-in

Warning: To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent
protection in accordance with the National Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit. To reduce the risk of fire, connect only to a circuit
provided with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.