Bulletin 1609 Industrial Uninterruptible Power Supply

7

Publication 1609-IN012B-EN-P - August 2012 DIR 10000234085 (Version 01)

Dry I/O Contacts

There is one Remote Enable/Disable Switch connection and 3 Dry I/O Contacts available on the front of the

UPS. Do not apply external power to the Remote Enable/Disable Switch; however, the 3 sets of Dry Contacts

required external power supplies (Contacts Rating is 1A/24 Vdc). Each of the dry contacts is used to provide a
remote status indication of the UPS, as follows:

1 and 2 On Battery Contact (NO)
3 and 4 Low Battery Contact (NO)
5 and 6 Fault

(Indicates UPS has faulted see the User Manual trouble

shooting section)
7 and 8 Remote Enable/Disable

(Closed for Output Enable, Open for Output Disable)

USB Communication Port

The UPS supports a USB communication port for the end user to connect with a computer. The

user may monitor all the UPS status through the USB port if the 1609 UPS Management Software is

installed in the computer. The software is stored in the CD and can be found in the accessory bag.

Manual or Remote Enable/Disable of UPS Output Selection

The 1609-D UPS output is designed to be manually or remotely Enabled or Disabled. User is required to

enable or disable the remote function switch on the front panel.

Selected 'DISABLE' for Manual Enable/Disable the UPS's Output.

Selected 'ENABLE' for Remote Enable/Disable the UPS's Output.

Manual Enable/Disable/Self-test

The Power Button on the front of the UPS is used to manually enable or disable the output of the 1609-D UPS.

To enable the 1609-D UPS, press and hold the Power Button until one beep is

heard.
To disable the 1609-D UPS, press and hold the Power Button until three beeps are

heard then release immediately (takes approximately 3 seconds).
To perform a self-test, press and hold the Power Button until two beeps are heard

then release immediately.

Remote Enable/Disable

An external switch connected to the Dry I/O terminals 7 and 8 is required to remotely Enable or Disable the

UPS output.

To enable the UPS, close the switch that is connected to the

Dry I/O terminals 7 and 8.

To Disable the UPS, open the switch that is connected to the

Dry I/O terminals 7 and 8.

8 7 6 5 4 3 2 1

REMOTE FUNCTION

ENABLE

DISABLE

8 7 6 5 4 3 2 1

R

R

R

SW

24 Vdc