Protection features, Safety features, Dielectric strength – Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual

Page 11

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM009A-EN-P — February 2014

11

Bulletin 1606 Switched Mode Power Supplies

11. Protection Features

Output over-current protection

not included

Reverse input polarity protection included

unit does not start when input voltage is reversed

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 3.6mm

e.g. screws, small parts

Over-temperature protection

not included

Input transient protection

not included

Output transient protection

included

see EMC section

Internal input fuse

not included

12. Safety Features

Input / output separation

no galvanic separation

200V epitaxial diode between input and output

Safety level of output voltage

The output voltage is regarded to be SELV (EN 60950-1) or PELV (EN 60204-1, EN
50178, IEC 60364-4-41) if the input voltage fulfills the requirements for a SELV
source or PELV source.

Class of protection

III

PE (Protective Earth) or chassis connection not required

PE resistance

< 0.1Ohm

between housing and chassis-ground terminal

13. Dielectric Strength

The input and output voltages have the same reference, are floating and have no ohmic connection to ground.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output
terminals together before conducting the test.
When testing, set the cut-off current settings to the value in the table below.

Fig. 13-1 Dielectric strength

A

Type test

60s

500Vac

Factory test

5s

500Vac

Field test

5s

500Vac

Cut-off current setting

> 2mA

A

Chassis

In- / Output

-

+

Advertising