Description, Specification quick reference, Catalog numbers – Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual

Page 2: Certification marks, Redundancy module

Advertising
background image

All parameters are specified at 24V, 20A output current, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.

2

Rockwell Automation Publication 1606-RM009A-EN-P - February 2014

Bulletin 1606 Switched Mode Power Supplies

Redundancy Module

Cost Effective Solution to Build Redundant Systems
Dual Input with Single Output
Two Diodes (Common Cathode)
DC12-48V (120V) ±25% Wide-range Input
Full Power Between -40°C and +60°C
Width only 32mm
Rugged Metal Housing
Quick-connect Spring-clamp Terminals
Easy Wiring:
Distribution Terminal for Negative Pole Included
3 Year Warranty

Description

The 1606-XLSRED is a redundancy module that can be
used to build 1+1 and N+1 redundant systems. It is
equipped with two input channels, which can be
connected to power supplies with up to 10A output
current and one output, able to carry nominal
currents up to 20A. The module is suitable for power
supplies with constant current overload behavior as well
as any kind of “Hiccup” overload behavior.

The 1606-XLSRED is the perfect solution to use in a
redundant system, if the power supply itself is equipped
with a DC-OK signal.
In addition to the 1606-XLSRED is the 1606-XLERED which
includes monitoring circuitry. LEDS and relay

contacts signal when one of the two DC-input voltages
is out of range due to a non-functioning power supply.

Another interesting application for the redundancy module
is to separate sensitive loads from non-sensitive loads.
This avoids the distortion of the power quality for
the sensitive loads which can cause controller failures.

Unique quick-connect spring-clamp terminals allow a
safe and fast installation and a large international
approval package for a variety of applications makes
this unit suitable for nearly every situation.

Specification Quick Reference

Input voltage

DC 12-48V

±25%

DC 12-120V

±25%

w/o restrictions
with restrictions

Input voltage
range

9-60Vdc
9-150Vdc

w/o restrictions
with restrictions

Input current

2x 0-10A

continuous

2x 0-16A

for 5 seconds

Output current

0-20A

continuous

20-32A

for 5 seconds

25A at

cont.

overload/

short circuit

Input to output
voltage drop

typ. 0.78V
typ. 0.85V
typ. 0.85V

input: 2x5A
input: 1x10A
input: 2x10A

Power losses

typ. 0W

at no load

typ.

7.8W

input:

2x5A

typ.

8.5W

input:

1x10A

typ.

17W

input:

2x10A

Temperature range -40°C to +70°C

operational,

Derating 0.5A/°C

+60

to

+70°C

Dimensions

32x124x102mm WxHxD

Catalog Numbers

Redundancy 1606-XLSRED 12-48V

(120V)

Module

Standard unit

Accessory 1606-XLB Wall/panel mount

bracket

Certification Marks

IND. CONT. EQ.

UL 508

UL 60950-1

Class I Div 2

IECEx

ATEX

II 3G Ex nA IIC T4 Gc

Marine

EMC, LVD

Marine RINA

GOST R

C-Tick

Advertising