Example: n+1 redundancy up to 30a, Example: battery back-up – Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual

Page 16

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

16

Rockwell Automation Publication 1606-RM009A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

17.4. Example: N+1 Redundancy up to 30A

N+1 Redundancy up to 30A requires four 10A power supplies and two 1606-XLSRED redundancy modules.

Fig. 17-2 Wiring diagram, n+1 Redundancy, 30A output current

optional

I

I

L

N

PE

I

1606-
XLSRED

Redundancy

Module

+

-

OUT

+

-

IN 1

+

-

IN 2

1606-
XLSRED

Redundancy

Module

+

-

OUT

+

-

IN 1

+

-

IN 2

L N PE

+ +

- -

Power

Supply

Adj

Overload

DCok

24V,10A

L N PE

+ +

- -

Power

Supply

Adj

Overload

DCok

24V,10A

L N PE

+ +

- -

1606-
XLS240EA

Power

Supply

Adj

Overload

DCok

24V,10A

Failure

Monitor

30A

Load

L N PE

+ +

- -

Power

Supply

Adj

Overload

DCok

24V,10A

I

Note: Use separate mains systems for each power supply whenever possible.

17.5. Example: Battery Back-up

A battery back-up with 10A requires one 10A power supply and one 1606-XLSRED redundancy module.

Please note:
Set output voltage of power supply to 26.5Vdc minimum to ensure that the load current is delivered from the power
supply and not from charger (battery). Use a fuse between battery and 1606-XLSRED.

Fig. 17-3 Wiring diagram, 10A Battery back-up

optional

L

N

PE

24V Battery

I

Battery

Charger

+

-

Failure

Monitor

10A

Load

L N PE

+ +

- -

1606-
XLS240EA

Power

Supply

Adj

Overload

DCok

24V,10A

1606-
XLSRED

Redundancy

Module

+

-

OUT

+

-

IN 1

+

-

IN 2

1606-
XLS240EA

1606-
XLS240EA

1606-
XLS240EA