Maintenance

4-3

1502-UM050D-EN-P – June 2013

3. HiPot test (Refer to Page 2-2)

• Check the vacuum bottle integrity.
• Check the insulation resistance.

4. Lubrication

• Using Aeroshell No. 7 (1 oz. tube, Part No. 40025-198-01) grease the

actuator plate where the overtravel springs and washers make contact
(Figure 4.2).

Insulator

Grease

Actuator Plates

Grease

Insulator

Grease

Actuator Plates

Grease

Figure 4.2 – Grease Locations

• Using Aeroshell No. 7 (1 oz. tube, Part No. 40025-198-01) grease the

pivot shaft at the bearing points on the mechanical latch mechanism
option (Figure 4.3).

Grease

Pivot Shaft

Grease

Pivot Shaft

Figure 4.3 – Mechanical Latch Grease Locations

NOTE: Do not grease the armature shaft plastic bearings. These bearings are
self-lubricating and do not require grease.