Rockwell Automation 1502 400 Amp Medium Voltage Contactor (Series D) User Manual

Page 45

Advertising
background image

Maintenance

4-17

1502-UM050D-EN-P – June 2013

8. Route the trip coil leads as shown in Figure 4.22 and reconnect them to the

auxiliary terminals. Secure the leads to the back panel of the housing with
wire ties. Refer to the appropriate wiring diagram in this manual if control
wiring details are required.

Access to Trip Coil

Lead Terminals

Trip Coil Leads

Access to Trip Coil

Lead Terminals

Trip Coil Leads

Figure 4.22 – Trip Coil Lead Routing

9. Replace the armature plate and the front stop. Position the front stop by

resting it lightly against the armature plate.

10. See the Mechanically Latched Contactor Set-up Procedure (page 4-18) for

establishing the position of the latch mechanism.