Maintenance
4-17
1502-UM050D-EN-P – June 2013
8. Route the trip coil leads as shown in Figure 4.22 and reconnect them to the
auxiliary terminals. Secure the leads to the back panel of the housing with
wire ties. Refer to the appropriate wiring diagram in this manual if control
wiring details are required.
Access to Trip Coil
Lead Terminals
Trip Coil Leads
Access to Trip Coil
Lead Terminals
Trip Coil Leads
Figure 4.22 – Trip Coil Lead Routing
9. Replace the armature plate and the front stop. Position the front stop by
resting it lightly against the armature plate.
10. See the Mechanically Latched Contactor Set-up Procedure (page 4-18) for
establishing the position of the latch mechanism.