DeviceNet 1732 ArmorBlock 16-Point I/O, Series A 13

Publication 1732D-IN002B-EN-E - January 2013

actuators and output devices, however, input devices will remain powered as long as the
DeviceNet power is on.

Refer to publication M115-CA001 for Rockwell Automation cable and cord set offerings
or access the Connection Systems website at:

www.ab.com/sensors/products/connection_systems/index.html

.

Wire the Module

Follow the wiring instructions for the ArmorBlock I/O modules.

Communicate with Your Module

This module’s I/O is exchanged with the master through a cyclic, polled, or
change-of-state connection.

Cyclic - allows configuration of the block as an I/O client. The block will produce and
consume its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O message to the
module. The module consumes the message, updates outputs, and produces a response.
The response has input data.

Change-of-State - productions occur when an input changes or a fault condition occurs. If
no input or fault condition change occurs within the expected packet rate, a heartbeat
production occurs. This heartbeat production tells the scanner module that the I/O
module is alive and ready to communicate. Consumption occurs when data changes and
the master produces new output data to the I/O block.

Refer to the Module Data Definitions table for more information. Note that the y
indicates all 1732D catalog numbers

1732D-IB16M12y Data Definitions

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Produce 0

17

16

15

14

13

12

11

10

Produce 1

115

114

113

112

111

110

19

18

Where: I = Input data